CQR Fike Twinflex Sound Point Red
Sounder with 85dB output
High & Low sounder adjustable
Three sound patterns
Inbuilt end of line set by DIL switch
Supplied with back box and flush mounting adaptor plate
The CQR Fike Twinflex Pro 2 Two-Wire Fire Alarm Panel is designed for compatibility with CQR Fike Twinflex devices. This adaptable system integrates Fike’s Twinflex Multipoint ASD, which utilizes both smoke and heat detection, and an optional built-in sounder. The entire system can be installed using just one pair of wires per zone, simplifying installations, speeding up the process, and reducing costs.
Device Type | Sounder : Red |
---|---|
IP Rating | IP21C |
Cable Type | Max 2 core 1.5mm screened fire rated cable, 500m (max per zone) |
Device Protocol | TWINFLEX V3 + TWINFLEX PRO |
Operating Standard | BS EN54-3 |
Operating Temperature | -10 to +50° C |
Wiring Style | 2-Wire Conventional |
Dimensions (mm) | 89 x 89 x 62mm (Surface) 89 x 89 x 34 (Flush) |
Device Loading Units | 13 |
Operating Volt Mains (Vdc) | 25.5 - 35 V DC |
Operating Volt Bat (Vdc) | 22 - 26V DC |
Quiescent Current (mA) | 0.185 mA |
Current Consumption (mA) | High 14.5 Low 12.6 mA |
Max Current (mA) | 14.5 mA |
Sound Output @1m (low) (db) | 65 + |
Sound Output @1m (high) (db) | 85+ |
Our enthusiastic team have decades of industry experience, contact them today for world-class support.