CQR Fike Twinflex Weatherproof Manual Call Point
IP65 weatherproof
Resettable element & key
Call point cover included
Back Box supplied
Inbuilt ‘End of Line’ set by DIL switch

Description

The CQR Fike Twinflex Pro 2 Two-Wire Fire Alarm Panel is designed for compatibility with CQR Fike Twinflex devices. This adaptable system integrates Fike’s Twinflex Multipoint ASD, which utilizes both smoke and heat detection, and an optional built-in sounder. The entire system can be installed using just one pair of wires per zone, simplifying installations, speeding up the process, and reducing costs.

Additional information

Device Type

IP65 Call Point

IP Rating

IP54* Not EN54 Tested

Cable Type

Max 2 core 1.5mm screened fire rated cable, 500m (max per zone)

Device Protocol

TWINFLEX V3 + TWINFLEX PRO

Operating Standard

BS EN54-11

Operating Temperature

-10 to +50° C

Wiring Style

2-Wire Conventional

Commodity Code

85319000

Country Of Origin

GB

Height (mm)

82

Width (mm)

117

Depth (mm)

115

Weight (kg)

0.35

Dimensions (mm)

87 x 87 mm

Device Loading Units

16

Operating Volt Mains (Vdc)

25.5 – 35 V DC

Operating Volt Bat (Vdc)

20 – 26V DC

Quiescent Current (mA)

50 uA

Current Consumption (mA)

16.5 mA

Max Current (mA)

16.5 mA

LED Operation : Alarm

Pulsed twice per second

LED Operation : EOL

5 second interval